I. Application Background
As a continuous power supply scenario requiring high reliability, data centers are equipped with high-power diesel generator sets as standby power. This project is fitted with 6 units of MTU 2MW high-speed diesel generator sets, with a total installed capacity of 12MW, serving as the critical standby power supply for the data center.
During emergency startup and loaded operation, high-power diesel engines generate exhaust gas with much higher emissions of nitrogen oxides (NOₓ) and particulate matter (PM) compared with small and medium-power units. Data centers are generally located within urban or industrial parks, adjacent to office and residential areas, and subject to local emission regulations for non-road mobile machinery and stationary pollution sources. Meanwhile, as green and low-carbon requirements for the data center industry keep tightening, exhaust gas treatment has become an indispensable part of data center construction and acceptance.
II. Emission Status and Treatment Target
According to the emission parameters of the generator sets:
III. Treatment Process Scheme: DPF + SCR Combined Process System
This project adopts a series layout of front-mounted DPF particulate filter and rear-mounted SCR denitrification. Each MTU 2MW unit is equipped with one set of aftertreatment device, and the 6 units are centrally managed via a unified control system.
Process flow: Engine exhaust → DPF particulate trapping unit → SCR catalytic reduction unit (including urea injection system) → Compliant discharge
IV. Value of the Solution
Compliance Value: Reducing NOₓ emissions from 3456 mg/Nm³ to below 120 mg/Nm³. It meets China’s regulatory requirements for non-road mobile machinery and local stationary source emission control, supporting EIA, project acceptance and long-term compliant operation of the data center. The system eliminates black smoke and controls ammonia slip, improving the visual environment of the park, reducing impacts on surrounding office and residential zones, and lowering risks of environmental complaints and rectification orders. It ensures stable performance under test-run conditions and high efficiency during full-load emergency operation, achieving both emission compliance and reliable power supply.
Centered on the DPF+SCR combined process, this project addresses the characteristics of MTU 2MW units featuring high raw NOₓ emission (3456 mg/Nm³) and stringent removal target (down to 120 mg/Nm³). Systematic design covers catalyst performance, injection control, flow field layout and system monitoring, offering a practical engineering approach for clean operation of generator fleets in large-scale data centers.